Xantrex PV100S-208 Manuel d'utilisateur Page 106

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 124
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 105
Specifications
A–2 152379 Rev C
System Specifications
The PV100S has been designed for photovoltaic power systems, which operate
within the following specifications.
Environmental Specifications
The following environmental specifications are the same for both models of the
PV100S 100 kW Grid-Tied Photovoltaic Inverter.
CAUTION: Equipment Damage
Operation of the PV100S in a manner other than specified in this manual may cause
damage to the PV100S and other system components and will void the terms of the
warranty.
Table A-1
Environmental Specifications
Specification Value
Dimensions
Inverter and DC Interface
Transformer and AC Interface
Overall System Footprint:
Layout Option A
Layout Option B
82 in H x 60 1/4 in W x 22 in D (208 cm H x 153 cm W x 56 cm D)
44 in H x 50 in W x 34 in D (112 cm H x 127 cm W x 86 cm D)
12 ft W x 6 ft L (approximate) (3.6 m W x 1.8 m L)
9 ft W x 7 ft L (approximate) (2.7 m W x 2.1 m L)
Weight
Inverter and DC Interface
Transformer and AC Interface
Overall Weight
1000 lbs (approximate)
1400 lbs (approximate)
2400 lbs (approximate)
Allowable Ambient Temperature
Operating
Storage
-20 °C to 50 °C Maximum
-40 °C to 50 °C Maximum
Relative Humidity To 95%, Non-condensing
Elevation Power Derated above 6600 ft
Clearance (ventilation and
serviceability)
In front of access doors: 36 in (91 cm)
In front of access panels: 36 in (91 cm)
Sides: 12 in (30 cm)
Back: 6 in (15 cm)
Maximum Distance between Main
Inverter Enclosure and AC Interface/
Transformer Enclosure
15 ft (4.5 m)
Vue de la page 105
1 2 ... 101 102 103 104 105 106 107 108 109 110 111 ... 123 124

Commentaires sur ces manuels

Pas de commentaire